Interior Climate Control

8.7

Inadequate Heating

Acceptable Performance/Condition
Heating systems shall be capable of maintaining an indoor air temperature of:
  a) 22°C in living spaces and
  b) 18°C in unfinished basements
  c) 15°C in crawl spaces;
at the design temperature for the geographical location.

Warranty
One -Year Work and Materials
Damage resulting from alterations, deletions or additions made by the homeowner and from improper maintenance is excluded from the warranty.

Action
Where the heating system is not capable of maintaining the prescribed temperature, repairs shall be made.

Remarks
Several factors affect living space temperatures:

Balancing the air delivery system may not completely compensate for the effects of these factors. In determining the temperature of a room, measurements shall be taken in the center of the room at 1,500 mm above the floor after the heating system has been running continuously for at least 20 minutes.
Heat loss calculations and duct designs assist in determining the furnace size and adequacy of the heating system.